IEC 60502-1 YVZ2V (NYRY) – 48

XLPE INSULATED, STEEL WIRE ARMORED, MULTI-CORE POWER CABLES

STANDARDS
IEC 60502-1

STRUCTURE

Conductor

Stranded Copper

Isolated

Cross-linked polyethylene

Filler

Polyvinyl Chloride

Armor

Galvanised Round Steel Wire

Outer Shield

Polyvinyl Chloride

TECHNICAL SPECIFICATIONS

Max. Operating Temperature

Max. Short Circuit Temperature

Test Voltage

3,5kV

Min. Bending Radius

12 x D

Single Cable Vertical Flame Propagation Test

Rated Voltage Uo/U

Unleaded

APPLICATION AREAS

Since it is suitable for heavy operating conditions resistant to mechanical stresses, it can be used under the ground. It adapts to high operating temperatures, is resistant to short-term sudden temperature increases and has a longer service life.

TECHNICAL DATA Cu/CR-PVC/CR-PVC
Nominal Section (mm2) Cable External Radius (mm) Approximate Net Weight (kg/km) Conductor Resistance Max ohm/km (20°C) Current Carrying Capacity (mm2)
YXZ2V In soil (A) In the air (A)
2x10 18 772 183 87 75
2x16 20 980 115 113 100
2x25 24,5 1530 0.727 146 136
2,35 27 1835 0.524 176 165
2x50 30 2270 0.387 208 201
2x70 33 2915 0.268 256 255
2x95 38 4025 0.193 307 314
2x120 41 4785 0,153 349 364
2x150 45 5670 0,124 391 416
2x185 50 7230 0.0991 442 480
2x240 56 9040 0.0754 509 565