IEC 60502-1 YXZ2V (N2XRY) 47

XLPE INSULATED, STEEL WIRE ARMORED, SINGLE CORE ENERGY CABLES

STANDARDS
IEC 60502-1

STRUCTURE

Conductor

Stranded Copper

Isolated

Cross-linked polyethylene

Filler

Polyvinyl Chloride

Armor

Galvanised Round Steel Wire

Outer Shield

Polyvinyl Chloride

TECHNICAL SPECIFICATIONS

Max. Operating Temperature

Max. Short Circuit Temperature

Test Voltage

3,5kV

Min. Bending Radius

12 x D

Single Cable Vertical Flame Propagation Test

Rated Voltage Uo/U

Unleaded

APPLICATION AREAS

It is used in direct underground applications in closed or open areas.

APPLICATION AREAS

It is used in direct underground applications in closed or open areas.

TECHNICAL DATA Cu/XLPE/PVC/SWA-AWA/PVC
Nominal Section (mm2) Cable External Radius (mm) Approximate Net Weight (kg/km) Conductor Resistance Max ohm/km (20°C) Current Carrying Capacity (mm2)
In soil (A) In the air (A)
YXZ2V
1x50 18 707 0,387 211 218
1x70 20 929 0,268 257 275
1x95 21 1194 0,193 304 336
1x120 24 1504 0,153 341 388
1x150 26 1794 0,124 377 438
1x185 28 2180 0,0991 418 501
1x240 31 2769 0,0754 469 508
1x300 33 3351 0,0601 514 654
1x400 37 4342 0,047 565 733
1x500 41 5475 0,0366 623 825
1x630 45 6937 0,0283 690 934