IEC 60502-1 YXZ2V (N2XRY) 49

XLPE INSULATED, STEEL WIRE ARMORED, MULTI-CORE POWER CABLES

STANDARDS
TS IEC 60502-1

STRUCTURE

Conductor

Stranded Copper

Isolated

Cross-linked polyethylene

Filler

Polyvinyl Chloride

Armor

Galvanised Round Steel Wire

Outer Shield

Polyvinyl Chloride

TECHNICAL SPECIFICATIONS

Max. Operating Temperature

Max. Short Circuit Temperature

Test Voltage

3,5kV

Min. Bending Radius

12 x D

Single Cable Vertical Flame Propagation Test

Rated Voltage Uo/U

Unleaded

APPLICATION AREAS

Since it is suitable for heavy operating conditions resistant to mechanical stresses, it can be used under the ground. It adapts to high operating temperatures, is resistant to short-term sudden temperature increases and has a longer service life.

APPLICATION AREAS

Since it is suitable for heavy operating conditions resistant to mechanical stresses, it can be used under the ground. It adapts to high operating temperatures, is resistant to short-term sudden temperature increases and has a longer service life.

TECHNICAL DATA Cu/XLPE/PVC/SWA/PVC
Nominal Section (mm2) Cable External Radius (mm) Approximate Net Weight (kg/km) Conductor Resistance Max ohm/km (20°C) Current Carrying Capacity (mm2)
In soil (A) In the air (A)
YXZ2V
3x10 19 875 1,83 87 75
3x16 21 1130 1,15 113 100
3x25 26 1790 0,727 146 136
3x35 28 2190 0,524 176 165
3x50 31 2725 0,387 208 201
3x70 37 3900 0,268 256 255
3x95 40 4900 0,193 307 314
3x120 44 5910 0,153 349 364
3x150 49 7440 0,124 391 416
3x185 54 8970 0,0754 509 565
3x240 60 11200 0,0754 50 565
3x300 69 14799 0,0601 632 580
3x400 82 18855 0,0470 756 663
3x25+16 29 1985 0,721/1,15 146 136
3x35+16 30 2353 0,524/1,15 176 165
3x50+25 34 3000 0,387/0,727 208 201
3x70+35 39 4150 0,268/0,524 256 255
3x95+50 43 5260 0,193/0,387 307 314
3x120+70 48 6590 0,153/0,268 349 364
3x150+70 53 8070 0,124/0,268 391 416
3x185+95 51 9620 0,0991/0,193 442 480
3x240+120 63 12210 0,0754/,0153 509 565