NYM (NVV) 05VV-U / 05VV-R

PVC INSULATED, PVC SHEATHED, MULTI-CORE INSTALLATION CABLES

STANDARDS
TS HD 21.4 S2
VDE 0250
IEC 60227

STRUCTURE

Conductor

Solid or Stranded Copper

Isolated

Polyvinyl Chloride

Filler

Polyvinyl Chloride

Outer Shield

Polyvinyl Chloride

TECHNICAL SPECIFICATIONS

Max. Operating Temperature

Max. Short Circuit Temperature

Test Voltage

2kV

Min. Bending Radius

12 x D

Single Cable Vertical Flame Propagation Test

Rated Voltage Uo/U

Unleaded

APPLICATION AREAS

It is used in humid places under plaster or on plaster installments.

TECHNICAL DATA Cu/PVC/PVC/PVC
Nominal Section (mm2) Cable External Radius (mm) Approximate Net Weight (kg/km) Conductor Resistance Max ohm/km (20°C) Current Carrying Capacity (mm2)
Lower Limit In the air (A)
(NVV) NYM / H05VV-U, H05VV-R
2x1,5 8,8 121 12,1 22
2x2,5 10,0 163 7,41 30
2x4 10,9 212 4,61 40
2x6 11,8 270 3,08 51
2x10 15,7 498 1,83 70
2x16 18,4 698 1,15 94
2x25 20,8 1001 0,727 119
2x35 23,4 1320 0,524 148
3x1,5 8,9 134 12,1 16,5
3x2,5 10,5 194 7,41 23
3x4 11,4 254 4,61 30
3x6 12,9 343 3,08 38
3x10 16,4 605 1,83 52
3x16 18,7 858 1,15 69
3x25 22,2 1156 0,727 90
3x35 24,5 1500 0,524 111
4x1,5 9,9 168 12,1 16,5
4x2,5 11,3 233 7,41 23
4x4 10,3 333 4,61 30
4x6 14,2 430 3,08 38
4x10 18,2 770 1,83 52
4x16 20,9 1106 1,15 69