STANDARDS
TS IEC 60502-1
DIN VDE 0276-603
It is used under the ground and in cable ducts where there is not much stress.
It is used under the ground and in cable ducts where there is not much stress.
TECHNICAL DATA | Cu/PVC/PVC | ||||||
---|---|---|---|---|---|---|---|
Nominal Section (mm2) | Cable External Radius (mm) | Approximate Net Weight (kg/km) | Conductor Resistance Max ohm/km (20°C) | Current Carrying Capacity (mm2) | |||
In soil | In the air (A) | ||||||
YVV-U (NYY), YVV-R (NYY) |
|
|
|
|
|||
1×4 | 7,01 | 87 | 4,61 | 59 | 50 | 45 | 33 |
1×6 | 7,51 | 109 | 3,08 | 73 | 62 | 59 | 43 |
1x10 | 8,65 | 158 | 1,83 | 97 | 83 | 81 | 60 |
1x16 | 9,60 | 219 | 1,15 | 125 | 107 | 110 | 82 |
1x25 | 11,00 | 319 | 0,727 | 161 | 138 | 146 | 110 |
1×35 | 12,10 | 417 | 0,524 | 192 | 164 | 181 | 137 |
1×50 | 13,80 | 556 | 0,387 | 227 | 195 | 219 | 167 |
1×70 | 15,30 | 761 | 0,268 | 278 | 238 | 281 | 216 |
1×95 | 17,60 | 1033 | 0,193 | 332 | 286 | 341 | 264 |
1x120 | 19,50 | 1787 | 0,153 | 377 | 325 | 396 | 308 |
1×150 | 21,00 | 1563 | 0,124 | 423 | 365 | 456 | 356 |
1×185 | 23,20 | 1942 | 0,0991 | 478 | 413 | 501 | 400 |
1×240 | 26,60 | 2528 | 0,0754 | 555 | 470 | 615 | 485 |
14300 | 29,20 | 3216 | 0,0601 | 627 | 541 | 709 | 561 |
1x400 | 35,20 | 1066 | 0,0470 | 725 | 614 | 852 | 656 |
1×500 | 39,80 | 5209 | 0,0366 | 818 | 608 | 982 | 710 |
1x630 | 46,20 | 6654 | 0,0283 | - | 777 | 1138 | 855 |