STANDARDS It is used under the ground and in cable ducts where there is not much stress. It is used under the ground and in cable ducts where there is not much stress.
TS IEEC 60502-1
DIN VDE 0276-60
TECHNICAL DATA
Cu/PVC/PVC /PVC
Nominal Section (mm2)
Cable External Radius (mm)
Approximate Net Weight (kg/km)
Conductor Resistance Max ohm/km (20°C)
Current Carrying Capacity (mm2)
In soil (A)
In the air (A)
YVV-U (NYY), YVV-R (NYY)
3x16+10
21,20
952
1,15/1,83
102
79
3x25+16
24,40
1363
0,727/1,15
133
106
3x35+16
26,80
1702
0,727/1,15
159
129
3x50+25
30,90
2310
0,387/0,727
188
157
3x70-35
34,40
2310
0,268/0,524
232
199
3x70-35
39,60
4209
0,193/0,387
280
246
3x120+70
43,90
5308
0,153/0,268
318
285
3x120+70
47,40
6253
0,124/0,268
359
326
3x120+70
52,40
7843
0,0991/0,193
406
374
3x240+120
59,90
10132
0,0991/0,193
473
445
PVC INSULATED, LOW VOLTAGE POWER CABLES
STRUCTURE
TECHNICAL SPECIFICATIONS
APPLICATION AREAS
APPLICATION AREAS