STANDARDS These cables, which have a very low dielectric loss, are used in buildings, pipes and industrial zones, or in distribution centers where mechanical damage is not expected, and in power plants where sudden load changes occur. It adapts to high operating temperatures, is more durable and has a longer service life. These cables, which have a very low dielectric loss, are used in buildings, pipes and industrial zones, or in distribution centers where mechanical damage is not expected, and in power plants where sudden load changes occur. It adapts to high operating temperatures, is more durable and has a longer service life.
TS IEC 60502-1
DIN VDE 0276-603
TECHNICAL DATA
Cu/XLPE/PVC/PVC
Nominal Section (mm2)
Cable External Radius (mm)
Approximate Net Weight (kg/km)
Conductor Resistance Max ohm/km (20°C)
Current Carrying Capacity (mm2)
In soil
In the air (A)
YXV (N2XY)
3x16+10
19,8
858
1,15/1,83
112
98
3x25+16
23,0
1247
0,727/1,15
145
133
3x35+16
25,4
1574
0,524/1,15
174
162
3x50+25
28,9
2117
0,387/0,727
206
197
3x70+35
32,8
2912
0,268/0524
254
250
3x95+50
37,2
3909
0,193/0,387
305
308
3x120+70
42,0
5018
0,153/0,268
348
359
3x150+70
45,2
5905
0,124/0,268
392
412
3x185+95
52,0
7677
0,0991/0,193
444
475
3x240+120
58,4
9776
0,0754/0,153
517
564
4x1,5
11,1
186
12,1
31
24
4x25
12,0
236
7,41
40
32
4x4
13,1
316
4,61
52
42
4x6
14,6
422
3,08
64
53
4x10
17,4
639
1,83
86
74
4x16
19,7
906
1,15
112
98
4x25
23,0
1333
0,727
145
133
4x35
26,1
1799
0,524
174
162
4x50
29,9
2404
0,387
206
197
4x70
34,4
3374
0,268
254
250
4x95
38,8
4509
0,193
305
308
4x120
44,2
5748
0,153
348
359
4x150
48,2
7013
0,124
392
412
4x185
53,6
8730
0,0991
444
475
4x240
62,3
11535
0,0754
517
564
XLPE INSULATED, LOW VOLTAGE POWER CABLES
STRUCTURE
TECHNICAL SPECIFICATIONS
APPLICATION AREAS
APPLICATION AREAS