STANDARDS Since it is suitable for heavy operating conditions resistant to mechanical stresses, it can be used under the ground. It adapts to high operating temperatures, is resistant to short-term sudden temperature increases and has a longer service life. Since it is suitable for heavy operating conditions resistant to mechanical stresses, it can be used under the ground. It adapts to high operating temperatures, is resistant to short-term sudden temperature increases and has a longer service life.
TS IEC 60502-1
TECHNICAL DATA
Cu/XLPE/PVC/SWA/PVC
Nominal Section (mm2)
Cable External Radius (mm)
Approximate Net Weight (kg/km)
Conductor Resistance Max ohm/km (20°C)
Current Carrying Capacity (mm2)
In soil (A)
In the air (A)
YVOV (NYRY)
2x10
20,5
900
1,83
90
66
2x16
22,5
1100
1,15
116
89
2x25
26,0
1650
0,727
150
118
2x35
28,0
1950
0,524
181
145
2x50
31,5
2500
0,387
215
176
2x70
35,5
3400
0,268
264
224
2x95
40,5
4360
0,193
317
271
3x10
21,5
1050
1,83
75
60
3x16
23,5
1300
1,15
98
80
3x25
27,5
1950
0,727
128
106
3x35
29,5
2350
0,524
157
131
3x50
33,5
3050
0,387
185
159
3x70
38,0
4200
0,268
228
202
3x95
43,0
5350
0,193
275
244
3x120
46,5
6400
0,153
313
282
3x150
52,0
8150
0,124
353
324
3x185
57,0
9750
0,0991
399
371
3x240
67,0
12250
0,0754
464
436