Cu/PVC/PVC – 6181 Y

PVC Isolated, Single core Cables

STANDARDS
TS EN 50525-2-31
BS EN 50525-2-31
IEC 60227-3

UK CODE
2491 X / 6491 X

STRUCTURE

Conductor

Solid or Stranded Copper

Isolated

Polyvinyl Chloride

Outer Shield

Polyvinyl Chloride

TECHNICAL SPECIFICATIONS

Max. Operating Temperature

Max. Short Circuit Temperature

Test Voltage

Min. Bending Radius

D 12 ise 5xD
D>12 ise 6xD

Single Cable Vertical Flame Propagation Test

Rated Voltage Uo/U

Unleaded

APPLICATION AREAS

It is used flush or surface mounted in fixed facilities, dry places, distribution boards and enclosed spaces, factories, workshops and all kinds of workplaces.

TECHNICAL DATA Cu/CR-PVC/CR-PVC
Nominal Section (mm2) Cable External Radius (mm) Approximate Net Weight (kg/km) Conductor Resistance Max ohm/km (20°C) Current Carrying Capacity (mm2)
In the air (A)
H03Z1Z1-F
1* re 3,9 26 18,1 13,5
1,5* re 4,4 33 12,1 17,5
2,5* re 5,0 46 7,41 24
4* rm 6 69 4,61 32
6* rm 6,5 89 3,08 41
10* rm 7,8 139 1,83 57
16* 9,1 207 1,15 76
25* 11 312 0,727 101
35* 12,1 410 0,524 125
50 13,8 557 0,387 151
70 15,6 761 0,268 192
95 18,2 1060 0,193 232
120 19,9 1307 0,153 269
150 21,8 1599 0,124 300
185 23,8 1977 0,0991 341
240 27,8 2608 0,0754 400
300 32,5 3355 0,0601 458

re: Single wire conductor
rm: Stranded conductor